LIHCH

Place of use

This type of cables are used as signal and data transmission cables in the connections of electronic control systems, sound frequency transmission. This type of cables is halogen-free, has flame -retarder and low smoke density.

 

Structure

Inner Conductor

Electrolytic Stranded Annealed Copper Wire, Class 5
EN 60228, IEC 60228, VDE 0295

Insulation

HFFR Compound EN 50290-2-26, DIN 47100 Colour Code

Stranding

Cores Twisted in Layers

Seperator

PES Tape

Screen

Tinned Copper Wire Braiding

Outer Sheath

HFFR Compound EN 50290-2-27, RAL 7001 Grey

 

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C

Technical Info


CONDUCTOR 
RESISTANCE
INSULATION
RESISTANCE
MUTUAL 
CAPACITY
IMPEDANCEINDUCTANCECURRENT 
CARRYING 
CAPACITY
OPERATING
VOLTAGE
TEST VOLTAGE
mm²
0,22
0,34
0,50
0,75
1,0
1,5
2,5
Ω/km
79
56
39
26
19,5
13,3
7,98
0,22 ve 0,34 mm² = 200
≥0,50 mm² = 20
mm²
0,22
0,34
0,50
0,75
1,0
1,5
2,5
pf/m
110
110
120
120
130
140
150
78Ω0,67 mH/km0,22
0,34
0,50
0,75
1,0
1,5
2,5
2,5
4,5
6,0
13
16
20
25
0,22 ve 0,34 mm² = 250 V
≥0,50 mm² = 300/500 V
0,22 ve 0,34 mm² = 1200 V
≥0,50 mm² = 2000 V
BENDING 
RADIUS
TEMPERATURE 
RANGE
FLAME RETARDANT 
TEST
EMC*SMOKE DENSITY 
TEST
TEST ON 
CORROSIVENESS
OF COMBUSTION 
GASES
HALOGEN FREE 
TEST
FLAME RETARDANT 
TEST
15XD-30ºC+70ºCIEC 60332-1-2
VDE 0482-332-1-2
EN 60332-1-2
ELECTROMAGNETIC 
COMPATIBILITY
IEC 61034-2
VDE 0482-1034-2
EN 61034-2
IEC 60754-2
VDE 0482-267-2-3
EN 50267-2-3
IEC 60754-1
VDE 0482-267-2-1
EN 50267-3-1
IEC 60332-3-24
VDE 0482-332-3-24
EN 60332-3-24